6 - 19 6 - 19
MELSEC
6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION
6.4.3 Connecting the connector for the coaxial cable
The following section explains how to attach the BNC connector (connector plug for
the coaxial cable) to the cable.
(1) Using a BNC connector manufactured by DDK Ltd.
The following explains how to connect the BNC-P-3-NiCAu or BNC-P-5-NiCAu to
the cable.
CAUTION
•
Correctly solder coaxial cable connectors. Incorrect soldering may result in
malfunction.
(a) Structure of the BNC connector and coaxial cable
Parts comprising the BNC connector
Nut
Washer
Gasket
Plug shell
Clamp
Contact
Structure of the coaxial cable
External conductor
Internal conductor
Outer sheath
Insulating material
(b) How to attach the BNC connector and the coaxial cable
1) Cut the portion of the outer sheath of the coaxial cable as shown in the
figure below.
A
Cut this portion of the outer sheath.
2) Fit the nut, washer, gasket, and clamp onto the coaxial cable, as
shown below, and then loosen the external conductor.
Clamp
Gasket
Washer
Nut
3) Cut the external conductor, insulation material and internal conductor
to the dimensions shown below. However, cut the external conductor
to the same dimension as the tapered section of the clamp and smooth
it down to the clamp.
Insulation
material
Internal
conductor
Clamp and
external conductor
C
B
Cable A
3C-2V
15mm (0.59 in.)
5C-2V, 5C-2V-CCY
10mm (0.39 in.)
Cable B
C
3C-2V
6mm
(0.24 in.)
3mm
(0.12 in.)
5C-2V, 5C-2V-CCY
7mm
(0.28 in.)
5mm
(0.20 in.)
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......