13.1 List of Error Messages in CC IE Control Utility
13.1.2 Error messages displayed on the setting screen
13
- 6
(7) Event setting screen
(8) Target setting screen
(9) Refresh parameter setting screen
Error message
Corrective action
The event No. is outside the range.
Please input a value within the range 0-63.
Set the value for the event number within the range of 0 to 63.
The device No. is outside the range.
Please input each device within the following ranges.
LB:0000-7FFF
LW:0000-1FFFF
LX:0000-1FFF
SB:0000-01FF
SW:0000-01FF
Set the values for the device number within the following
ranges to each device specified by device codes.
LB:0000-7FFF
LW:0000-1FFFF
LX:0000-1FFF
SB:0000-01FF
SW:0000-01FF
The device size is outside the range.
Please input it on the following conditions.
Input within the range of 1-64. (device No. + device size - 1)
must not exceed the upper bound of device No.
Set the value for the device size within the range of 1 to 64,
and (device No. + device size - 1) should not exceed the
maximum value of the device number.
The word device is outside the range.
Please input a value within the range 1-65535.
Set the value for the word device within the range of 1 to
65535.
The event No. XX is overlapping. Please correct the
settings.
Set the event numbers not to overlap.
Error message
Corrective action
The logical station number setting value is outside the
range.
Please input a value within the range 0-239.
Set the value for the logical station within the range of 0 to 239.
The network No. setting value is outside the range.
Please input the value within the range 1-239.
Set the value for the network number within the range of 1 to
239.
The station number setting value is outside the range.
Please input a value within the range 0-120.
Set the value for the station number within the range of 0 to
120.
The logical station number XX is overlapping.
Please correct the settings.
Set the logical station numbers not to overlap.
Specification of PLC is unsuitable. Please specify PLC.
Specify the programmable controller CPU.
Error message
Corrective action
Link side number of points is out of range.
Set it within the range of XX to YY.
Set the value for link side number of points within the range of
XX to YY.
Link side start device No. is out of range.
Set it within the range of XX to YY.
Set the value for link side start device number within the range
of XX to YY.
Link side end device No. is out of range.
Set it within the range of XX to YY.
Set the value for link side end device number within the range
of XX to YY.
Device setting is overlapping.
Correct these settings.
Set the device ranges not to overlap.