41 Correction of outdoor
temperature
Function setting value: 0 to 14
Correction of outdoor temperature: -7°C to 7°C (1°C intervals)
7
When No. 36 Outdoor temperature
indication and No. 37 Indoor temper-
ature indication are set to
Show
, set
the correction value of the tempera-
ture shown on the controller.
Example: If the temperature
detected by the built-in thermistor
is 20°C and the correction value is
+3°C (the function setting value is
10), the temperature indicated by the
controller will be 23°C.
Note
- The indication value is not cor-
rected when
Lo
or
Hi
is displayed.
- Correction values are not reflected
to the control (such as Auto
By-pass) using outdoor/indoor
temperatures.
42 Correction of indoor
temperature
Function setting value: 0 to 14
Correction of indoor temperature: -7°C to 7°C (1°C intervals)
7
57 External output setting
1
—
Exhaust
air fan
monitor
Supply
air fan
monitor
Supply
air
after-
heater
—
—
—
—
— —
1
Set the ON/OFF conditions of termi-
nal block TM3 9–10.
[1] Exhaust air fan monitor:
The output turns ON/OFF in line
with the operation/stop of the
exhaust air fan. (The operation is
the same as ON/OFF operation
by the controller.)
[2] Supply air fan monitor:
The output turns ON/OFF in line
with the operation/stop of the
supply air fan. (Depending on the
conditions such as outdoor tem-
peratures, the output can be off
automatically.)
[3] Supply air after-heater:
The output turns ON 10 seconds
after the supply air fan operation./
The supply air fan stops three
minutes after the output is turned
OFF.
- Set the setting when supply air
after-heaters are connected.
58 External output setting
2
—
By-pass
ventila-
tion
monitor
Supply
air pre-
heater
—
—
—
—
—
— —
1
Set the ON/OFF conditions of termi-
nal block TM3 7–10.
[1] By-pass ventilation monitor:
The output turns ON/OFF in line
with the status (By-pass/Heat
exchange ventilation) of the ven-
tilation mode. (The output turns
ON/OFF in line with the operation
of the built-in By-pass damper.)
[2] Supply air pre-heater:
The output turns ON 10 seconds
after the supply air fan operation./
The supply air fan stops three
minutes after the output is turned
OFF.
- Set the setting when supply air
pre-heaters are connected.
- The output turns OFF when the
outdoor temperature is 15°C or
higher.
- The output ON/OFF conditions
can be changed by the function
settings Nos. 59 and 60.