─ 90 ─
Damper lead
Damper connector: CN7 Power circuit board
[4] Remove the damper lead from the metal plate hook of
the control box (indicated by ).
[5] Disconnect the damper lead connector from the power
circuit board.
Damper assembly Damper lead Bypass air duct
[6] Remove the element guide (SA). ... Refer to (4) [3].
[7] Remove the damper assembly.
[8] Remove the damper lead from the bypass air duct.
Circuit board
Circuit board
(5) Remove the damper assembly
[1] Remove the heat exchanger. ... Refer to (2).
[2] Remove the PCB cover. ... Refer to (3).
[3] Lower the circuit board (control circuit board) to provide
a work space for disconnecting and connecting the
connectors.
b. Lower the circuit board.
a. Remove the circuit board fixing screws from the bot-
tom side of the product.
(2 screws: Spl screw PT 4X10 (painted), indicated by )
Tightening torque
: 1.5 ± 0.2 N.m