Specification may be subject to change without notice.

DATE

TYPE

Heat Recovery Ventilator  LOSSNAY

MODEL

VL-350CZPVU-R-E

5/6

SAFETY NOTES

12-Jan-21

NUMBER

N19SGGD0003B

Caution for installation

Ventilation design

1.

For the outside air intake vent, choose a position where combustion gas or other similar exhaust air is not sucked 
in and the vent is not buried by snow.

2.

Do not install the product at locations where the product is prone to be damaged from salt or hot springs. Failure 
to heed this warning may result in malfunction of product.

3.

Do not install the product at locations where toxic gas or gas containing corrosive components such as acids, 
alkaline, organic solvents, or paints is generated.

4.

Do not install the product near bedrooms.

5.

For living rooms (e.g. bedrooms) where it is anticipated that building ambient noise will be below 30 dB(A), use 
commercially available ducts that have sound deadening qualities on the supply air side.

6.

Install supply air and exhaust air grills at locations where they are less likely to reverberate.

7.

In cold regions or regions with strong winds, wind outside sometimes gets inside when operation of the product is 
stopped. So, we recommend providing a motorized shutter midway along the supply air and exhaust air ducts.

8.

Install the product so that discharged gas or exhaust air from burning appliances and equipment does not flow 
back inside the product.

9.

Use an outdoor hood, that makes it less likely for rain water, snow or small animals (e.g. bats) from entering the 
ends of the supply air and exhaust air ducts.

10. At the outdoor hood installation position, allow at least 3x the diameter of the duct through holes between the 

outdoor hood and the ducts so that exhaust air is not mixed in with supply air. (Preferably a distance of 450 mm 
or more should be ensured between the outdoor hood and the ducts.)

11. In areas where the outdoor air is below -20

, electric shutters(local supply) is required in the OA duct in addition 

to the pre-heater. With the pre-heater, the OA temperature must be higher than -15

.

12. Do not use duct booster fan on the RA/EA duct or the OA/SA duct. If an external force is applied to the built-in 

bypass damper, the damper may be fixed on the bypass side, when it is switching between Lossnay mode and 
Bypass mode, and heat recovery may be prevented.

Installing the Lossnay unit

1.

The unit is exclusively vertical mounting type.

2.

Do not install the product in hot places in the direct sunlight and in smoky places.

3.

Do not install the Lossnay unit or the remote controller in a bathroom or other humid location.

4.

Install the product and the duct piping on the indoor side of the insulation layer/airtight layer.

5.

Install the product (on the wall) in the direction of the duct connecting flange so that it is horizontal (within 

±

1

°

).

Features of Lossnay

1.

A Lossnay unit provides 24-hour ventilation for the entire house. The heat recovery system provides fresh air at a 
comfortable air temperature.

2.

With simple wall-mount design, the units can be easily installed in compact places in houses such as the roof 
space, hallway cupboard, kitchen, etc.

3.

Airflow can be adjusted within the range between 25% and 100% by 1% to meet the designed airflow rate.

4.

Lossnay can be monitored and controlled via MELCloud from anywhere an internet connection is available.

*MELCloud is a Cloud-based solution for controlling Lossnay either locally or remotely by computer, tablet or 

smartphone via internet.

5.

The quiet operation is achieved with the fan designed for only th

i

s model.  

6.

Optional high efficiency filters can be installed inside the unit without any filter box, which saves space.

7.

By using 0-10V signal from the controller(local supply) such as the humidistats and CO2 sensors, the airflow of 
the Lossnay unit can be changed.  It is also connected to the light switch(local supply) and can change to the 
boost operation(Input 220-240V). It allows the fan speed to automatically change according to the bathroom 
occupation, the CO2 level, and the humidity level. 

8.

It is possible to select manual switching or automatic switching between "Lossnay ventilation (with heat 
exchange)" and "By-pass ventilation (without heat exchange)".

9.

Operating temperature range is down to -15

. With a pre-heater, it is available down to -25

Summary of Contents for VL-350CZPVU-R-E

Page 1: ... h L s External static pressure Pa dB ErP Class Specification may be subject to change without notice DATE TYPE Heat Recovery Ventilator LOSSNAY MODEL VL 350CZPVU R E 90 150 74 38 14 1 6 35 26 19 15 SPECIFICATIONS 12 Jan 21 NUMBER N19SGGD0003B Sound Pressure level 3m A Temperature exchange efficiency Dimensions Height x Width x Depth 89 62 44 85 87 88 27 Heat recovery ventilation Bypass ventilatio...

Page 2: ...itchen 5 wet rooms Kitchen 6 wet rooms SPECIFICATIONS 30 Breakout 37 39 Air flow rate l s 21 29 37 45 53 61 0 0 20 0 40 0 60 0 80 0 100 0 120 0 60 65 70 75 80 85 90 95 0 50 100 150 200 250 300 350 0 100 200 300 400 500 Exchange efficiency Static pressure Pa Air volume 100 70 50 30 L s m3 h 55m 40m 25m φ150mm dia straight pipe length Attention Mitsubishi Electric measures figures in the chart accor...

Page 3: ... Guide EA Synthetic Resin Synthetic Resin 14 Drain pipe EA Synthetic Resin 15 Drain pipe SA Synthetic Resin 23 Air Supply Fan Synthetic Resin 18 Wall Mount Hook Top Galvanized Steel 16 PCB Under Cover Steel sheet Munsell 6 2PB 8 8 1 6 24 Air Supply Fan Motor DC 12 25 Air Exhaust Fan Synthetic Resin 04 Filter Cover SA Synthetic Resin Synthetic Resin Painted metal Munsell 6 2PB 8 8 1 6 13 10 Pipe Gu...

Page 4: ...otary switch 10 digit TAB1 TAB2 Connector Power supply SA2 Address setting rotary switch 1 digit TAB3 4 Connector Reactor SW2 SW5 to SW7 Switch TAB5 not in use CN9 CN10 Connector Fan motor SYMBOL Terminal block CN17 to CN20 Connector Connectoron PCB CN105 Connector IT Definition of symbols Attention 1 Electrical work must be carried out safely and reliably by a professional electrical contractor p...

Page 5: ...ust be higher than 15 12 Do not use duct booster fan on the RA EA duct or the OA SA duct If an external force is applied to the built in bypass damper the damper may be fixed on the bypass side when it is switching between Lossnay mode and Bypass mode and heat recovery may be prevented Installing the Lossnay unit 1 The unit is exclusively vertical mounting type 2 Do not install the product in hot ...

Page 6: ... air preheaters supply air after heaters that do not have temperature control functions select duct heaters that have the appropriate capacity according to the airflow passing through the heaters Drain piping 1 Be sure to connect drain piping by the following procedure to prevent freezing and dew condensation forming on the surface of the piping Connect the drain piping on the indoor side of the i...

Page 7: ...0 350CZPVU E Declaration of Conformity N20SGGT0062 VL 250 350CZPVU E Filter Replacement Manual 876H07701 VL 250 350CZPVU E Instruction Manual 876H46401 VL 250 350CZPVU E Parts List U295_0_DB VL 250 500CZPVU E Installation Manual 876H46502 VL 350CZPVU R E Specification Sheet N19SGGD0003B VL CZPVU R L E Homeowner Quickstart Guide Commissioning Logbook ...

Page 8: ......

Reviews: