8
–
1.3 Operation control function by the remote controller
(1) Switching sequence of the operation mode switches of remote controller
Dehumidifying
Cooling
Fan
Heating
(2) [CPU reset]
When the “CHECK” and “GRILL” buttons on the remote controller are pressed at the same time, this function is activated.
This function is same as power supply reset.
(3) [Power failure compensation function]
• This function becomes effective when “POWER FAILURE COMPENSATION SET” is valid by setting the remote controller
functions.
• The remote controller's status is always stored in memory, and after recovery of power, operation is resumed according to
the memory contents. However the auto swing stop position and timer mode are cancelled, but the weekly timer setting is
restored with the holiday setting through all weekdays.
By resetting the clock and cancelling the holiday setting for each weekday after recovery of power, weekly timer setting
becomes effective.
• Contents stored in memory for power failure compenstion are as follows.
Note (1) Item
➅➆
and
➇
are stored in memory regardless of whether the power failure compensation setting is valid or invalid, and silent mode setting is
cancelled regardless of whether the power failure compensation setting is valid or invalid.
➀
Running or Stopping status just before power failure
If it had been operating under OFF timer mode or simple timer mode, memorzed status is as stopping (At the
recovery of power, the timer mode is cancelled but weekly timer setting is changed to the holiday setting through all
weekdays
➁
Operation mode
➂
Fan speed mode
➃
Room temperature setting
➄
Louver auto swing/stop
However, the stop position (position 4) is cancelled and is becomes the level position (position 1).
➅
“Remote control function items”, set with the remote controller function setting (“Indoor unit function items” are
stored in the inoor unit's memory.)
➆
Upper limit value and lower limit value set by temperature setting control.
➇
Clock timer setting and weekly timer setting (Other timer settings are not sotred in memory).
[Parts layout on remote controller PCB]
X
Y
SW2
SW1
A
B
M
S
親
子
SW1
SW2
Control selector switch (SW1)
Switch
Function
SW1
M
Master remote controller
S
Slave remote controller
Note (1) SW2 is not normally used, so do not change the selection.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...