40
-
2 SYSTEM TROUBLESHOOTING PROCEDURE
2.1 Basics of troubleshooting
Basic troubleshooting is to check/analyze/save data by connecting the Mente PC.
Whenever arriving at the site, always connect the Mente PC before starting work.
Method of error data analysis (Basic procedure)
• Identify whether particular error occurred during operation or stopping.
• Is it caused by the installation conditions of outdoor/indoor unit? (Refrigerant quantity, pipe length, short-circuit, clogged
filter, etc.)
• Isn’t there any beginner’s mistake at the installation? (Wrong address, mistake in piping or wiring, etc.)
• Is the failure related to any hardware (parts)? (SV main body, coil, capillary, check valve, sensor, etc.)
• Is it a major component.
Compressor, inverter PCB and outdoor DC fan motor.
• Is it a failure of electrical component?
Error on
indoor unit or
outdoor unit?
Indoor unit
Outdoor unit
Is the remote
controller
connected?
Was the power
supply reset after the
error occurred?
Check and write down the
momentary data (retained in
before the error occurred
the remote controller) just
Save the data for 30 minutes
before the error occurred
in Mente PC
Connect the Mente PC
and restart operation
Save the momentary data
just before the error
occurred
in Mente PC
Connect the Mente PC
and restart operation
Connect the Mente PC
and restart operation
Connect the Mente PC
and restart operation
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...