42
–
2.3 Contents of troubleshooting
(a) List of inspection displays
1) Indoor and outdoor units
Remote
controller
error code
7-segment
display
Name of inspection
Classification
Page
E1
–
Remote controller communication error
Communication error
59
E2
–
Duplicated indoor unit address
Address setting error
60
E3
–
Outdoor unit signal line error
Address pairing setting error
61
E5
–
Communication error during operation
Communication error
62
E6
–
Indoor heat exchanger temperature thermistor anomaly (Thi-R) Thermistor wire breakage
63
E7
–
Indoor return air temperature thermistor anomaly (Thi-A)
Thermistor wire breakage
64
E9
–
Drain trouble
System error
65
E10
–
Excessive number of indoor units (more than 17 units) by
controlling one remote controller
Communication error
66
E12
–
Address setting error by mixed setting method
Address setting error
67
E16
–
Indoor fan motor anomaly (FDT series)
DC fan motor error
68
–
Indoor fan motor anomaly (FDK series)
DC fan motor error
69
E19
–
Indoor unit operation check drain motor check mode anomaly Setting error
70
E28
–
Remote controller temperature thermistor anomaly (Thc)
Thermistor wire breakage
71
E30
E30
Unmatch connection of indoor and outdoor unit
System error
72
E31
E31
Duplicated outdoor unit address No.
Address setting error
73
E32
E32
Open L3 Phase on power supply at primary side
Site setting error
74
E36
E36-1
Discharge pipe temperature error (Tho-D1)
System error
75
E36-3
Liquid flooding anomaly
System error
76
E37
E37-1, 2
E37-5, 6
Outdoor heat exchanger temperature thermistor (Tho-R)
and subcooling coil temperature thermistor (Tho-SC, -H)
anomaly
Thermistor wire
breakage
77
E38
E38
Outdoor air temperature thermistor anomaly (Tho-A)
Thermistor wire breakage
78
E39
E39-1
Discharge pipe temperature thermistor anomaly (Tho-D1)
Thermistor wire breakage
79
E40
E40
High pressure anomaly (63H1-1 activated)
System error
80
E41 (E51) E41 (E51)-1 Power transister overheat
System error
81
E42
E42-1
Current cut (CM1)
System error
82
E43
E43-1
E43-2
Excessive number of indoor units connected, excessive total
capacity of connection
Site setting error
83
E45
E45-1
Communication error between inverter PCB and outdoor
control (PCB)
Communication error
84
E46
E46
Mixed address setting methods coexistent in same network
Address setting error
85
E48
E48-1
E48-2
Outdoor DC fan motor anomaly
DC fan motor error
86
E49
E49
Low pressure anomaly
System error
87
E53/E55
E53/E55-1 Suction pipe temperature thermistor anomaly (Tho-S),
Under-dome temperature thermistor anomaly (Tho-C1)
Thermistor wire
breakage
88
E54
E54-1
E54-2
High pressure sensor anomaly (PSH)/Low pressure sensor
anomaly (PSL)
Thermistor wire
breakage
89
E56
E56-1
Power transitor temperature thermistor anomaly (Tho-P1)
Thermistor wire breakage
90
E58
E58-1
Anomalous compressor by loss of synchronism
System error
91
E59
E59-1
Compressor startup failure (CM1)
System error
92
E60
E60-1
Rotor position detection failure (CM1)
System error
93
E63
E63
Emergency stop
Site setting error
94
2) Optional controller in-use
SL-1N-E
SL-2N-E
SL-3N-E
Indoor unit
control PCB
Outdoor unit
control PCB
Location of
trouble
Description of trouble
Repair
method
Error
code
Red
LED
Red
LED
Green
LED
Red
LED
Green
LED
E75
Keeps
flashing
Stays
OFF
Keeps
flashing
Stays
OFF
Keep
flashing
SL-1N-E
SL-2N-E
SL-3N-E
・
Communication enor (Deflective comm-
unication circuit on the main unit of
SL1N-E, SL2N-Eor SL3N-E)
Replacoment
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...