9
–
1.4 Operation control function by the outdoor controller
(A) Normal control
(1) Operation of major functional components under each operation mode
Operation mode
Fonctional item
Cooling/Dehumidifying
Fan
Heating
Thermostat
ON
Thermostat
OFF
Defrost
Thermostat
ON
Thermostat
OFF
Compressor (CM)
〇
×
×
〇
×
〇
Magnetic contactor CM1 (52X1, 52X2)
〇
〇
×/〇
〇
〇
〇
Outdoor unit fan mortor (FMo-1)
〇
×/〇
×/〇
〇/×
×/〇
〇→×
Outdoor unit fan mortor (FMo-2)
〇/×
×/〇
×/〇
〇/×
×/〇
〇→×
4 way valve (20S)
×
×
×
〇
〇
〇→×
Heating electronic expansion valve
(EEVH)
Fully open
Fully open
※
Opening Angle
Control
※
Fully closed /
Fully open
Super cooling coil electronic expansion
valve (EEVSC)
Opening Angle
Control
Fully closed Fully closed Fully closed Fully closed Fully closed
Solenoid valve (SV1) (oil return)
〇/×
×
×
〇/×
×
〇/×
Solenoid valve (SV6) (fluid return)
〇/×
〇/×
×
〇/×
〇/×
〇/×
Solenoid valve (SV11) (gas bypass)
×
×
×
〇/×
×
×
Crankcase heater (CH)
〇/×
〇/×
〇
〇/×
〇/×
〇/×
Note (1) It means
〇
: ON,
×
: OFF,
〇/×
: -,
×/〇
: ON or OFF.
(2) This shows the state of output when all indoor units are under the same mode.
(3)
※
1 : When stopped from cooling, it is fully open
When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control at the
stop.
※
2 : When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control at the
stop.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...