199
*
-
Setting value for allocation of external input function
Name
Purpose (Factory default)
Specification
Operating side connector
With external input terminals
closed
With external input terminals opened
Invalid
Invalid
Valid
Valid
Valid
Test run start
Cooling
Valid
External input CnS1
External input CnS2
External input CnH1
External input CnG2
External output CnZ1
External output CnH
External output CnY
External operation input (
Closed at shipping)
Demand input (
Closed at shipping)
Cooling / Heating forced input (Opened at shipping)
Silencing mode input (Opened at shipping)
Spare output (External output)
Operation output
Error output
Non-voltage contactor (DC12V)
Non-voltage contactor (DC12V)
Non-voltage contactor (DC12V)
Non-voltage contactor (DC12V)
DC12V output
DC12V output
DC12V output
NICHIATSU B02B-XAMK-1 (LF) (SN)
NICHIATSU B02B-XARK-1 (LF) (SN)
NICHIATSU B02B-XAEK-1 (LF) (SN)
NICHIATSU B02B-XASK-1 (LF) (SN)
MOLEX 5566-02A-RE
MOLEX 5286-02A-BU
MOLEX 5266-02A
Valid
Valid
Invalid
Invalid
Invalid
Normal
Heating
Invalid
"0" : External operation input
"1" : Demand input
"2" : Cooling/heating forced input
"3" : Silent mode input
"4" : Spare
"5" : Outdoor fan snow guard control input
"6" : Test run external input 1 (equivalent to SW5-1)
"7" : Test run external input 2 (equivalent to SW5-2)
"8" : Silent mode 2
"9" : Spare
By changing the allocation of external input functions (P07-19) on the 7-segment, functions of external
input terminals may be selected. Inputting signals to external input terminals enable the following functions.
"0" : Operation output
"1" : Error output
"2" : Compressor ON output
"3" : Fan ON output
"4-9" : Spare
The external output function of CnZ1 can be changed by
changing the setting in P06 on the 7 segment display panel.
Control selecting method
Content of control
7-2. Selection of controls
7-3. External input and output terminals specifications
*1 Control is switched when both the allocation of external input function (P07-10) and SW are changed.
(Example: To use CnS1 for the input of forced cooling mode, set P07 at 2 and SW3-7 at ON. To use CnS2 for the input of forced cooling mode, set P08 at 2 and SW3-7 atON.)
*2 In the energy saving mode, the capacity restriction becomes effective even if no signals are input at external input terminals.
SW setting on PCB
SW5-5
J13: Closed (Factory default), J13:
J15: Closed (Factory default), J15: Opened
P
○○
on 7-segment
SW3-7 to ON=1 *1
SW5-1 to ON + SW5-2 to ON
SW5-1 to ON + SW5-2 to OFF
Cooling test run
Heating test run
Communication method selection ON: Previous SL communication, OFF: New SL communication
External input selection (CnS1, CnS2 only) Closed: Level input, Opened: Pulse input)
Defrost selection Closed: Normal defrosting, Opened: Forced defrosting
Outdoor unit fan snow protection control ON time setting - 30 sec (at shipping) 10, 30-600 sec
Energy saving mode *2 OFF: Disabled (at shipping) 000, 040, 060, 080 [%]
Silencing mode setting 0 (at shipping) - 3: Larger values for larger effect
Allocation of external output (CnZ1)
Allocation of external input (CnS1)
Allocation of external input (CnS2)
Allocation of external input (CnG1)
Allocation of external input (CnG2)
Spare
Pump down operation
Operation priority selection
SW4-5:OFF, SW4-6:OFF*1 80% (Factory default)
SW4-5:ON , SW4-6:OFF*1 60%
SW4-5:OFF, SW4-6:ON*1 40%
SW4-5:ON , SW4-6:ON*1 00%
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
ー
Close the fluid operation valve on outdoor unit and set as follows:
(1) SW5-2 on PCB to ON
(2) SW5-3 on PCB to ON
(3) SW5-1 on PCB to ON
Forced cooling mode
(It can be fixed at cooling with external input terminals opened, or at heating with them closed.)
Set external input function
allocation to "2" *1
Set allocation of external
input function to "1" *1
Inputting signals to external input terminals selects the demand mode.
(J13 short-circuited: Level input, J13 open: Pulse input)
0: First push priority (at shipping)
1: Last push priority
Outdoor unit fan snow protection control
0: Control disabled (at shipping)
1: Control enabled
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
〜
Controls of outdoor unit may be selected as follows using the dip switches on the PCB and P
○○
on the 7-segment.
To change P
○○
on the 7-segment, hold down SW8 (7-segement display increment up: 1-digit), SW9 (7-segment increment up: 10-digit) and SW7 (Data write/Enter).
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...