33
–
(c) Saving of Operation Data
Mainly for investigating the causes of market claims, operation data are always saved in memory. If any trouble occurs,
the data writing is stopped and only the operation data prior to the time when the trouble occurs are recorded. These data
can be loaded to a PC via RS232C connector of PCB and utilized for identifying causes.
(i) Operation data for a period of 30minutes prior to the present operation are saved and updated continuously.
(ii) If an anomalous stop occurs, the data are not updated any more.
(iii) Data are written in based on 1 minute sampling interval and following data is transmitted to PC upon demand.
Data
Data range
Example
Software version
Ascii 15 bytes
KD3C218######## (# : NULL)
PID (Program ID)
Ascii 2 bytes
5D
Outdoor unit capacity
Ascii 3 bytes
As listed blow
Power supply frequency
Ascii 2 bytes
60
Outdoor address
Ascii 2 bytes
00 ~ 3F
Indoor address × 16 units
Ascii 2 bytes × 16 units
40 ~ 7F
Indoor capacity × 16 units
Ascii 3 bytes × 16 units
022 ~ 280
Outdoor unit composition
Outdoor unit capacity data
Remarks
Single type
Example: 10HP - [S10]
S: Display with Horse Power of single type
(iv) Error retention and monitoring data
Code
No.
Write contents
Record data
Data write range Unit of write Number of bytes
Contents
00 Indoor 1 Th
I
-A
–14 ~ 50
A/D value
1
Return air
01 Indoor 1 Th
I
-R1
0 ~ 72
A/D value
1
Heat exchanger 1
02 Indoor 1 Th
I
-R2
0 ~ 72
A/D value
1
Heat exchanger 2
03 Indoor 1 Th
I
-R3
0 ~ 72
A/D value
1
Heat exchanger 3
04 Indoor 1 EEV
0 ~ 470
1 pulse
2
05 Indoor 1 operation/stop
0,1
–
1
0
Stop
1
Operation
06 Indoor 1 operation mode
0 ~ 4
–
1
0
Auto
1
Dehumidifying
2
Cooling
3
Fan
4
Heating
07 Indoor 1 request Hz
0 ~ 255
1Hz
1
08 Indoor 1 answer Hz
0 ~ 255
1Hz
1
09 Indoor 1 indoor local
–
–
1
Bit0
Anti-frost
Bit1
EEV opening angle
implementation
10 Indoor 1 Thi spare
–14 ~ 50
A/D value
1
Discharge
11 Indoor 1 type
0 ~ 67
–
1
0
FDT
1
FDK
2
Others
3
FDE
4
FDTC
5
6
7
60 ~
12 Indoor 1PID
–
–
1
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...