38
*
–
Code
No.
Write contents
Record data
Data write range
Unit of
write
Number
of bytes
Contents
99
Heating setting 2 (Target high
pressure)
3.15 ~2.75
0.05
[MPa]
1
100
Heating setting 3 (Judgment
temperature)
30 ~ 38
1 [°C]
1
<Other>
104
Override number
0 ~
–
1
<Indoor unit information>
106
Registered indoor 1 – 8 operation
mode
0 ~ 4
–
8
0
Auto
1
Humidifying
2
Cooling
3
Fan
4
Heating
107
Registered indoor 1 – 8 request Hz
0 ~ 255
1Hz
8
108
Registered indoor 1 – 8 answer Hz
0 ~ 255
1Hz
8
Compressor stop cause (Cord No. C68)
It shows the latest comprressor anomalous stop cause
Compressor stop cause
No
At power on
0
Sensor disconnection
and/or short-circuit
Outdoor air temperature
1
Outdoor heat exchanger temperture 1
2
Outdoor heat exchanger temperture 2
3
Discharge pipe temperature sensor 1(CM1)
4
Suction pipe temperature sensor
5
Sub-cooling temperature sensor 1(liquid side)
6
Sub-cooling temperature sensor 2(gas side)
7
Under-dome temperature sensor 1
8
Power transistor temperature sensor 1
9
Active filter temperature sensor
10
High pressure sensor
11
Low pressure sensor
12
Anomaly detection
HP anomaly
20
LP anomaly
21
Td1 anomaly
22
FMo1 anomaly
23
FMo2 anomaly
24
Inverter 1 current cut
25
Inverter 1 startup failure
26
Inverter 1 communication error
27
Inverter 1 anomalous compressor induced voltage and torque
28
Inverter 1 power tansistor overheat
29
Inverter 1 rotor lock
30
Liquid flooding anomaly
31
Stop by restriction
Outdoor operation mode heating/cooling switching
40
Heating overload protection
41
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...