45
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Earth leakage breaker activated
Stays Off Stays Off
Stays Off Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
Is insulation
of respective harnesses OK?
YES
Check of the outdoor unit grounding wire and earth leakage breaker
�
Run an independent grounding wire from the grounding screw
of outdoor unit to the grounding terminal on the distribution
panel. (Do not connect to another grounding wire.)
�
In order to prevent malfunction of the earth leakage breaker
itself, confirm the conformity of high harmonic regulation.
* Insulation resistance of compressor
• Immediately after installation or when the unit has been left
for long period without power supply, the insulation
resistance may drop to a few M
Ω
because of refrigerant
migrated in the compressor.
When the earth leakage breaker is activated at lower insulation
resistance, check the following points.
�
6 hours after power ON, check if the insulation resistance
recovers to normal.
When power ON, crankcase heater heat up compressor and
evaporates the refrigerant migrated in the compressor.
�
Check if the earth leakage breaker is conformed to higher
harmonic regulation or not.
Since the unit has inverter, it is necessary to use components
conformed to high harmonic regulation in order to prevent
malfunction of earth leakage breaker.
YES
Check the outdoor unit grounding
wire and earth leakage breaker
Is any hamess bitten
between pannel and casing
or etc?
NO
YES
Are the
insulation resistance
and and coil resistance of
compressor OK?
Replace compressor. *
Secure insulation
resistance.
Secure insulation
resistance.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Compressor anomaly
• Noise
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...