(4) Remote controller display during the operation stop
(a) “Centralized control ON” is displayed always on the LCD under the “Center/Remote” and “Center” modes during the
operation stop (Power ON). This is not displayed under the “Remote” mode.
(b) If this display is not shown under the “Center/Remote” mode, check if the indoor unit power switch is turned on or not.
(5) Hot start (Prevention of cold draft during heating)
At the startup of heating operation, at resetting the thermostat, during defrosting operation and at returning to heating, the
indoor fan is controlled by the indoor heat exchanger temperature (detected with Th
I
-R) to prevent the cold draft.
Judgment by heating start thermostat
Normal condition/Set airflow volume
Thermostat OFF
Thermostat ON
Compressor OFF
Compressor ON
End of defrosting
Heat exchanger temp. 35
˚C
or higher, or after 7 minutes
Heat exchanger temp. 35
˚C
or higher, or after 7 minutes
Defrosting start
Fan
Lo
Lo
Set airflow volume
Set airflow volume
Indoor heat exchanger temp. (˚C)
Indoor heat exchanger temp. (˚C)
35
35
45
25
35
Indoor heat exchanger temp. (˚C)
Set airflow volume
Fan
OFF
Lo
25
35
45
Set airflow volume
Fan
OFF
Indoor heat exchanger temp. (˚C)
Fan
Lo
(
1
)
Note (1) Heating preparation is displayed during the hot start (when the compressor is operating and the indoor fan does not provide the set airflow volume).
(6) Hot keep
Hot keep control is performed at the start of the defrost control.
(a) Control
1) When the indoor heat exchanger temperature (detected with Th
I
-R1 or R2) drops to 35°C or lower, indoor fan is
changed to the lower tap at each setting.
2) During the hot keep operation, the louver horizontal control signal is transmitted.
(b) Ending condition
When the indoor fan is at the lower tap at each setting, it returns to the set airflow volume as the indoor heat exchanger
temperature rises to 45°C or higher.
(7) Fan control during the heating thermostat OFF
When the heating thermostat is turned OFF, the setting of the fan control is selectable with using the indoor function of wired
remote controller [Heating fan control].
(a) Low speed (Factory default)
If the indoor heat exchanger temperature drops 35°C or lower with the heating thermostat OFF, the indoor fan operate at
the lower speed tap at each setting.
(b) Set airflow volume
Even if the indoor heat exchanger temperature drops 35°C or lower with the heating thermostat OFF, the indoor fan
continues to run at the set airflow volume.
(c) Intermittent operation
If the indoor heat exchanger temperature drops 35°C or lower with the heating thermostat OFF, the indoor fan operates at
the lower speed tap at each setting and, when the indoor heater exchanger temperature drops 25°C or lower, the indoor fan
stops for 5 minutes. Then the fan runs at the slow speed tap for 2 minutes, and the judgment is made by the thermostat.
(d) Stop
If the indoor heat exchanger temperature drops 35°C or lower with the heating thermostat OFF, the indoor fan is turned
OFF. The same applies also when the remote controller sensor is effective.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...