50
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Power supply system anomaly
(Power supply to indoor unit PCB)
Stays Off Stays Off
Stays Off
2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
YES
YES
Is
AC 220-240V/220V
detected between L-N on
the indoor terminal
block?
Note (2)
Remove
transformer for
other than FDT and
FDTC series (CNW1)
Note (3) LM: Louver motor
FM: Fan motor
Note (4)
�
for GND
Is
AC 380/415V
for 3-phase unit detected
between L1, L2 and L3 on the
outdoor tarminal block
respectively?
Are fuses OK?
(2 pcs)
Is power
supply between
�
-
�
of
CNW0 OK?
Is
DC5V detected
between
�
-
�
of
CNW2?
Is power
supply to FM, LM and etc.
OK?
Note (1)
FDT and FDTC series: F200, F201
Other than FDT and FDTC: Fuse between wires
(1)
(2)
(3)
(4)
Other than FDT and
FDTC series
FDT and FDTC series
Is DC18V or higher
detected between Red-
Red (CNW2) at the
transformer secondary
side?
Outdoor Noise filter PCB
anomaly
Replace it
Wrong wiring or broken
wires between outdoor and
indoor units
Indoor power PCB
anomaly
Replace it
Replace FM, LM and etc.
Replace fuse
Indoor power PCB anomaly
Replace it
Indoor control PCB
anomaly
Replace it
Replace transformer
Indoor control PCB
anomaly
Replace it
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Wrong connection or breakage
of connecting wires
• Blown fuse
• Transformer anomaly
• Indoor power PCB anomaly
• Broken harness
• Indoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...