52
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(1)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(In case that is kept
on displaying on the remote
controller for more than 2
minutes after power ON)
Diagnosis
Countermeasure
NO
NO
NO
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
YES
YES
YES
YES
is kept on
displaying on the remote
controller for more than 2
minutes after power ON
Once turn OFF the breaker
and turn ON it again at 3
minute after power OFF
Isn't
the power fuse (5A) on the
outdoor control PCB
blown?
Is
the connection of wire
between noise filter and
inverter PCBs OK?
Are
the wires between indoor
and outdoor units
connected properly ?
Is
AC220-240V detected
between L-N at indoor
teminal block?
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at outdoor
terminal block?
Does
indoor green LED keep
flashing?
Does
indoor green LED flash
2 times?
Is
AC380-415V detected at
the secondary side of
noise filter PCB terminal?
Does it become normal?
Replace fuse
WAIT
Refer next page
Replace noise filter PCB
Connect wires correctly
Indoor control PCB anomaly
Replace it
Indoor/outdoor control PCB
anomaly
Replace it
Remote controller anomaly
Replace it
Breakage of wires for remote
controller
Replace it
Correct the connecting wires
between indoor and outdoor
units
Outdoor control PCB anomaly
Replace it
Breakage of connecting wire
Noise
Indoor control PCB anomaly
Replace it
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note:
(1)
When anomaly occurs during establishing communication betweeen indoor and outdoor unit, error code E5 is displayed (outdoor red LED
flash 2-times)
In case of E5, the way of troubleshooting is same as above mentioned (except for checking of connecting wire)
When reset the power after E5 occurs, if this anomaly recurs,
WAIT
is displayed on remote controller. If power ON/OFF is repeated in
a short period (within 1 minute),
WAIT
may be displayed. In such case, please wait for 3 minute after the power breaker OFF.
(2)
If any error is detected 30 minutes after displaying
“
WAIT
”
on the remote controller, the display changes to
“
INSPECT I/U
”
.
WAIT
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...