53
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(2)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(In case of fuse blown, how
to check the unit before
replacement of fuse)
Diagnosis
Countermeasure
YES
YES
NO
NO
YES
NO
Isn't
there any short circuit
between phases of noise
filter?
Isn't
there any crack or damage
on power transistor
module or diode stack?
Isn't
there any anomaly on
reactor?
Replace noise filter
Replace reactor
Replace inverter PCB
Replace fuse
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note: