54
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(3)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(No display on the remote
controller after power ON)
Diagnosis
Countermeasure
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
No display on the remote
controller after power ON
Does
indoor green LED keep
flashing?
Does
outdoor red LED flash
2-times?
Is
the connecting wires
between indoor and outdoor
units comnnected
properly?
Is
AC380-415V detected
between L1-L2, L2-L3,
L3-L1 respectively at outdoor
terminal block?
Is
AC220-240V detected
between L-N at indoor
teminal block?
Is
The fuse on indoor control
PCB OK?
Is
AC18V or higher is
detected between Red-
Red at secondary side of
indoor transformer? (1)
Is
DC10-11V between
X-Y at indoor control PCB
side when removing
remote controller ?
Note (1) except FDT
and FDTC
Fuse blown
Replace fuse
Transformer anomaly
Remote controller wire
short-circuited
Remote controller anomaly
Indoor control PCB
anomaly
Remote controller anomaly
Brakage of connecting
wires of remote controller
Correct the connecting
wires properly
Outdoor control PCB
anomaly
Replace it
Breakage of connecting
wire Noise
Indoor control PCB
anomaly
Replace it
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...