56
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(5)
Stays OFF Stays Off
Stays OFF Stays Off
1. Applicable model
5. Troubleshooting
All models
(In case that LED on outdoor
control PCB stays OFF)
Diagnosis
Countermeasure
In case that LED on
outdoor control PCB stays
OFF
Is
power fuse (5A) on the
outdoor conrol PCB
blown?
Is
AC380-415V detected at
secondary side of noise
filter?
Are
connecting wires between
noise filter and inverter PCB
connected properly?
Is
the connection of
connecting wire of reactor
OK?
Is
there any anomaly on
outdoor fan motor?
Once turn OFF the breaker
and turn ON it again at 3
minute after power OFF
Does it become normal?
Check inverter before
replacement of 52C
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
A
B
Normal
(Malfunction by temporary
noise)
Refer next page
Replace noise filter
Connect the connecting
wire properly
Correct connection
(In case of breakage of
wire replace it)
Outdoor control PCB
anomaly
Replace it
Outdoor fan motor
anomaly
Replace it
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...