58
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
〔
No display
〕
[No display]
Stays OFF Stays Off
Stays OFF Stays Off
1. Applicable model
5. Troubleshooting
All models
(No display on the remote
controller after power ON)
Diagnosis
Countermeasure
NO
NO
NO
YES
YES
YES
No display on the remote
controller after power ON
Is DC10V
or higher between X-Y
detected at remote
controller terminal?
Is DC10V
or higher between X-Y
wires detected when
removing remote
controller?
Are
connecting wires between
indoor and outdoor units
connected properly?
Remote controller anomaly
Remote controller anomaly
Correct connecting wire
Indoor control PCB
anomaly
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note: