59
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E1
-
Remote controller
communication error
Keeps flashing Stays Off
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the power
supply reset?
Does
the drain pump start
automatically at one
minutes after power
ON?
Turn SW7-1 OFF.
�
ON
Disconnect the wire
�
between indoor and outdoor
units
YES
YES
NO
Note (1) SW7-1: OFF
�
ON
Note (2) Does the remote controller displays “Internal check ON” even
after 3 minutes?
Reset power supply
(2)
(1)
NO
Malfunction by temporary
noise.
Check peripheral
environment
Indoor control PCB
anomaly
Replace it
Remote controller
anomaly
Replace it
2. Error detection method
When normal communication
between remote controller and
indoor unit is interrupted for
more than 2 minutes (Detectable
only with the remote controller)
3.
Condition of error displayed
Same as above
4. Presumable cause
• Anomalous communication
circuit between remote
controller and indoor unit
• Noise
Note:
If the indoor unit cannot communicate normally with the remote controller for 180 seconds, the indoor unit PCB starts to
reset automatically.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...