63
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E6
-
Indoor heat exchanger
temperature thermistor anomaly (Thi-R)
Keeps flashing 1 time flash
Keeps flashing
Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the connector of
thermistor connected
properly ?
Regarding the characteristics of
the thermistor, see the following chart
Are
the characteristics
of thermistor OK?
*1
NO
NO
YES
*1 Check several times to prove any poor connection
YES
Tempearture thermistor resistance (kΩ)
Temperature-resistance characreristics of indoor heat
exchanger temperature thermistor (Thi-R1, R2, R3)
5kΩ at 25ºC
Temperature (ºC)
Insert the connector
securely
Replace thermistor
(Thi-R)
Replace indoor control
PCB
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Thi-R1, R2, R3
3. Condition of error displayed
• If -50ºC or lower is
detected for 5 seconds
continuously, compressor
stops. After 3-minute delay,
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
• Or if 70ºC or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Anomalous connecion
of indoor heat exchanger
temperature thermistor
• Indoor heat exchanger
temperature thermistor
anomaly
• Indoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...