64
–
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E7
-
Indoor return air
temperature thermistor anomaly (Thi-A)
Keeps flashing 1 time flash
Keeps flashing
Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the connector of
thermistor connected
properly ?
Regarding the characteristics of
the thermistor, see the following chart
Temperature-resistance characreristics of indoor
return air temperature thermistor (Thi-A)
Are
the characteristics
of thermistor OK?
*1
NO
NO
YES
YES
*1 Check several times to prove any poor connection
15
10
5
0
10
30
40
20
50
Temperature thermistor resistance (k
Ω
)
Temperature (°C)
5kΩ at 25
°C
Insert the connector
securely
Replace thermistor
(Thi-A)
Replace indoor control
PCB
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Thi-A
3. Condition of error displayed
• If -50°C or lower is
detected for 5 seconds
continuously, compressor
stops. After 3-minutes delay
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
• Or if 48°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Anomalous connection of
indoor return air temperature
thermistor
• Indoor return air temperature
thermistor anomaly
• Indoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...