Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
67
–
E12
-
Address setting error
by mixed setting method
Keeps flashing Keeps flashing
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't the
automatic setting and
manual setting mixed in the address
setting method for indoor
units?
YES
NO
Review address setting.
Replace indoor control
PCB.
2. Error detection method
Automatic address setting and
manual adress setting are mixed
when setting adress of indoor
units
3.
Condition of error displayed
Same as above
4. Presumable cause
Mistake in address setting for
indoor unit
Note:
Address setting method list (Figures in [ ] are for Previous superlink models)
Models for new superlink protocol
Models for Previous superlink protocol
Indoor unit address setting Outdoor unit
address setting Indoor unit address setting
Outdoor unit
address setting
Indoor unit No. SW
Outdoor unit No. SW Outdoor unit No. SW
Indoor unit No. SW
Outdoor unit No. SW Outdoor unit No. SW
Manual address setting
(New SL)
000-127
00-31
00-31
00-47
00-47
00-47
(Previous SL
)
[00-47]
[00-47]
[00-47]
Automatic address setting
for single refrgerant system
(New SL)
000
49
49
49
49
49
(Previous SL
)
Automatic address setting
for multiple refrgerant systems
(New SL)
000
49
00-31
Not available
(Previous SL
)
Not available
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...