Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
68
–
E16
-
Indoor fan motor anomaly
(FDT series)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
FDT series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan
propeller?
Is DC280V
detected between
�
-
�
of
fan motor connector
CNM?
Does it become normal?
Is the fuse F202 blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
NO
YES
Reset the power supply and restart.
(1)
Note (1)
�
is GND
Remove foreign matter.
Replace the fan motor.
Check power supply
voltage.
Replace fan motor and
power PCB.
Replace fan motor. (If
the anomaly persists after
replacing the fan motor,
replace the indoor control
PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by revolution speed of
indoor fan motor
3.
Condition of error displayed
When actual revolution speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 2-seconds delay, fan
motor starts again automatically,
but if this anomaly occurs 4
times within 60 minutes after
the initial detection.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan propeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...