Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
70
–
E19
-
Indoor unit operation check,
drain motor check mode anomaly
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Indoor control PCB
anomaly
(Anomalous SW7)
Replace
Turn SW7-1 on the indoor
control PCB OFF and reset
the power
2. Error detection method
E19 occurs
3.
Condition of error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
Due to forgetting to turn OFF
SW7-1 after indoor operation
check)
Note:
Indoor operation check/drain pump check mode
If the power is ON after SW7-1ON. indoor operation check/drain pump check mode can be established.
1) When the communication between remote controller and indoor PCB is established 15 seconds after power ON, it
goes to indoor operation check.
2) When the communication between remote controller and indoor PCB is not established, it goes to drain pump check
(CnB connector should be open before power ON)
Is SW7-1
on the indoor control
PCB ON?
E19 occurs when the
power ON
NO
YES