Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
72
–
E30
E30
Unmatch connection of
indoor and outdoor unit
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
wiring connection between
indoor and outdoor units
correctly?
YES
NO
Is
the voltage
between L1-N at the terminal
block on indoor unit
AC220/240V?
NO
Is the voltage
between L1-L2, L2-L3
and L3-L1 at the terminal brock on
outdoor unit AC380/415V
respectively?
YES
YES
NO
Correct the wiring
Replace outdoor control
PCB
Disconnection or breakage
of wire between indoor and
outdoor unit
Replace indoor unit PCB
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Indoor control PCB anomaly
• Outdoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...