Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
73
–
E31
E31
Duplicated outdoor unit address No.
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Does E31 recur?
Check outdoor address No.
in the same superlink system
Reset the power supply
and restart operation.
Save data for 30 minutes before
stopping in Mente PC
Does the same
address No. exist?
YES
YES
NO
NO
Check and save the data of
operating condition.
Check the conditions
whether it occurs
immediately after the power
on or during operation.
Check the current address
Nos. of outdoor units.
Test run
*No action is taken because
it is judged that the power
reset is not done after
changing address
Correct address.
Replace outdoor control
PCB. *
* Before replacement,
please confirm whether
the rotary switch for
address setting is not
damaged.
(It was experienced that
No. 5 on rotary switch
was not recognized.)
2. Error detection method
When the microcomputer of
outdoor control PCB recognizes
the dupplicated address No. by
scanning all adresses of outdoor
units in the same superlink
system.
3.
Condition of error displayed
When duplicated outdoor unit
address No. exists in the same
superlink system.
4. Presumable cause
• Mistake in the address setting
of outdoor units
• More than 129 indoor units
connected
[
Maximum number can be set
by address switch is 128 units
]
• No setting of Master/Slave
setting switch for combination
use
Note: After taken above measure, reset the power and confirm no error is displayed occurs.
Unless the power is reset after changing address, the set address will not be confirmed.
In case of combination use, set the same address to both master and slave units. Distinction of master or slave unit is done by
setting SW4-7. (Refer the instruction manual and technical manual for details)
Caution:
Unless the power is reset after changing
address, the set address will not be
confirmed.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...