6
–
(14) Anomalous fan motor (FDT and FDK only)
Fan motor will be stopped with displaying “E16”, if it has detected the revolutions of 200 rpm or less continuously for 30
seconds at a rate of 4 times within 60 minutes, after starting the motor.
(15) High ceiling control [Applicable type: FDT, FDTC, FDTW, FDTS and FDE]
When the indoor unit is installed at a high ceiling, the airflow volume mode control can be changed with the indoor function of
wired remote controller “High ceiling setting”.
Setting
Standard (Shipping)
High Ceiling 1
High Ceiling 2
Remote controller setting
Hi Me Lo
Hi Me Lo
Hi Me Lo
Fan speed
Hi Me Lo
UHi1
Hi Me
UHi2
Hi Me
Note (1) It is set at Standard at the shipping from factory.
(2) At the hot start, heating thermostat OFF, or other, the indoor fan operate at the slow speed tap at each setting.
(16) Hot start
Indoor fan motor control is performed at the start of heating operation.
(a) When the temperature detected with the indoor heat exchanger thermistor (Th
I
-R1 or Th
I
-R2) drops 35°C or lower, it
control the fan with AC motor: Lo and DC motor: ULo.
(b) When the heat exchanger thermistor detects 45°C or higher with the fan running at Lo/ULo, it returns to the set airflow
volume.
Set airflow volume
Lo/ULo
35°C
45°C
Heat exchanger thermistor temp. (Th
I
-R1 or R2)
(c) On the indoor unit of which the thermostat has been turned OFF during heating operation, the fan is turned OFF if the
heat exchanger thermistor temperature (Thi-R1 or Thi-R2) drops 25°C or lower.
(17) Detection room temperature compensation during heating
With the standard specification, the compressor is turned ON/OFF based on the setting temperature of thermostat. However,
when the thermostat OFF is likely to occur earlier because the unit is installed in a condition that warm air tends to accumulate
near the ceiling, the setting can be changed by using the indoor function of wired remote controller “Heating room temperature
compensation”. Since the compressor is turned ON/OF at one of the setting temperature at +3, +2 or +1°C, the feeling of
heating can be improved. However, the upper limit of setting temperature is 30°C.
Operation
Setting temperature
Room temp. (deg)
–1
+1
Stop
Standard
Compressor
Operation
Setting temperature
Room temp. (deg)
+4
+2
Stop
With setting at +3°C
Compressor
(18) Return air temperature compensation
This is the function to compensate a difference between the detected temperature of the Return air thermistor and the measured
temperature after installation of unit.
(a) It is adjustable in the unit of 0.5°C by using the indoor function of wired remote controller “Return air thermistor
compensation”.
• +1.0°C, +1.5°C and +2.0°C
• −1.0°C, −1.5°C and −2.0°C
(b) Since the compensated temperature is transmitted to the remote controller and the outdoor unit, it is controlled with the
compensated temperature.
Note (1) Compensation of detection temperature is effective for the indoor unit sensor only.
(19) External control (Remote display)/Remote operation
Always connect the wired remote controller. Otherwise, you cannot perform the remote operation.
(a) Output for external control (remote display)
(Optional remote RUN/STOP monitor kit can be utilized.)
Following output connectors (CNT) are provided on the indoor control PCB. Connect the remote RUN/STOP monitor kit
and pick up respective dry contact signal.
•
Operation output
: Outputs DC12V relay drive signal during operation.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...