Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
79
–
E39
E39-1
Discharge pipe temperature
thermistor anomaly (Tho-D1)
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connector of
thermistor connected
properly?
Are the
characteristics of
thermistor
OK? *3
*3
Check several times to prove any poor connection
Temperature-resistance characteristics of discharge
pipe temperature thermistor (Tho-D1)
Save data for 30 minutes before stopping in Mente PC
YES
NO
NO
YES
Temperature (°C)
Temperature thermistor
resistance (kΩ)
0
20
40
60
80
100
120
140
160
180
200
0
20 40
60
80 100 120 140 160
Check and save the data of
operating condition.
Check the conditions whether
it occurs immediately after the
power on or during operation
or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value.
Insert the connector securely
Replace thermistor
(Tho-D1).
Replace outdoor control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-D1
3.
Condition of error displayed
•
If 3°C or lower is detected for
5 seconds continuously within
10-minutes to 10-minutes
20-seconds after the compressor
ON, the compressor stops. And after
3-minutes delay, the compressor
starts again automatically, but if this
anomalous temperature is detected
3 times within 40 minutes after the
initial detection.
4. Presumable cause
• Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
• Disconnection of thermistor
harness connection
(connector)
• Outdoor control PCB anomaly
Note:
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...