Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
81
–
E41(E51)
E41(E51)-1
Power transistor overheat
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the
connection of power
transistor temperature thermistor
OK?
(Check short-circuit or breakage
of harness)
Is the
characteristics of power transitor
temperature thermistor OK? *
* Refer the characterristics
of power transistor temperature
thermistor to E56 (page 90)
Is the fixing
of power transistor OK?
(Check tightening of screws or
application of radiation
silicon)
Save data for 30 minutes before stopping in Mente PC
Does the outdoor fan run ?
Does the
error recur when restarting?
Is the
cooling fan for inverter running?
Is 15V
of power for control PCB
detected?
Reset power supply and restart
After power OFF
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Check and save the data of
operating conditions
Check the temperature of
power transistor
Check the operation of
outdoor fan and cooling fan
Repair it according to the
troubleshooting procedure
of E48
Check it as much as
possible under the operating
conditions for 30 minutes
before error occurred
Wait and see.
Continue to obain data, if
possible (Keep connecting
the Mente PC)
If the cooling fan does not
run in spite of the operation
ON range, check the
voltage at the connector of
cooling fan.
If the 220/240V is detected,
repalce cooling fan motor.
If 0V is detected, replace
outdoor control PCB
After checking the loose
connection of connetor
or breakage of harness,
replace inverter PCB
Connect the connector of
thermistor securely.
Or replace power transistor
temperature thermistor
Replace power transistor
temperature thermistor
Fix power transistor on to
the radiation fin with proper
application of radiation
silicon
Replace power transistor
2. Error detection method
When anomalously high
temperature is detected by
power transistor temperature
thermistor (Tho-P1)
3.
Condition of error displayed
Anomalously high temperature
of power transistor is detected 5
times within 60 minutes (E41).
Or it is detected for 15 minutes
continuously
(E51)
4. Presumable cause
• Power transistor anomaly
• Power transistor temperature
thermistor anomaly
• Improperly fixing of power
transistor to radiator fin
• Inverter PCB anomaly
• Outdoor fan motor anomaly
• Anomalous cooling fan motor
for inverter
• Inadequate installation space
of outdoor unit
Note:
The operating conditions of cooling fan for inverter is shown in the right figure.
If the error does not recur, connect the Mente PC and continue to collect data.
81°C
Power transistor thermistor temperature
OFF
ON
85°C
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...