Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
88
–
E53/E55
E53/E55-1
Suction pipe temperature thermistor anomaly (Tho-S),
Under-dome temperature thermistor anomaly (Tho-C1)
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Check and save the data of
operating conditions
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
Check the sensed value.
Compare the temperature
on Mente PC with actual
measured value
Insert the connector
securely
Replace thermistor
(Tho-S or Tho-C1)
Replace outdoor control
PCB
2. Error detection method
Detection of anomalously low
temperature (resistance) of
Tho-S or Tho-C
3.
Condition of error displayed
• if -50°C or lower is detected
for 5 seconds continuously
within 2 minutes to 2 minutes
20 seconds after compressor
ON, compressor stops. When
the compressor is restarted
automatically after 3-minutes
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
•
Broken thermistor harness or
the internal wire of sensing
section (Check the molded
section as well)
•
Disconnection of thermistor
harness connection
(connector)
•
Outdoor control PCB
anomaly
Note:
E53: Tho-S, E55-1: Tho-C1
5kΩ at 25Cº
Temperature (Cº)
Tempearture thermistor resistance (kΩ)
NO
NO
YES
YES
Save data for 30 minutes before stopping in Mente PC
Is
the connector of
thermistor connected
properly ?
Are
the characteristics
of thermistor OK?
*1
Regarding the characteristics of
the thermistor, see the following chart
Temperature-resistance characreristics of
suction pipe temperature thermistor (Tho-S)
Temperature-resistance characreristics of
under-dome temperature thermistor (Tho-C1)
*1 Check several times to prove any poor connection
Temperature (Cº)
Tempearture thermistor resistance (kΩ)
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80 100 120 140 160
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...