Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
89
–
E54
E54-1, 2 *1
High pressure sensor anomaly (PSH)
Low pressure sensor anomaly (PSL)
Keeps flashing
Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is anomalous
pressure detected?
Is the
connector of the
sensor inserted
properly to the connector on
the outdoor control
PCB?
Save data for 30 minutes before stopping in Mente PC
Reset the power and restart operation.
Check the data for 30 minutes before stopping
YES
YES
NO
High pressure sensor
output characteristics
Sensor output Black (GND) – White; Output voltage (Black – Red; DC5V)
Pressure (MPa)
Pressure (MPa)
Low pressure sensor
output characteristics
NO
NO
NO
YES
E54
Does it recur?
Does
the pressure
converted from the
sensor output voltage match the
actual pressure measure
by pressure
gauge?
YES
Output voltage (V)
Output voltage (V)
Check and save the data of
operating conditions
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
Check the sensed value.
Insert the connector
securely and restart
operation
Temporary malfunction by
noise.
Correct if the source of
noise is specified.
Replace sensor (PSH, PSL)
Replace outdoor control
PCB
2. Error detection method
Detection of anomalous pressure
(valtage) of PSH or PSL
Operation range
High pressure : 0-4.15MPa
Low pressure : 0-1.7MPa
3.
Condition of error displayed
If anomalous sensor output
voltage (0V or lower or 3.49V
or higher) is detected for 5
seconds within 2 minutes to 2
minutes 20 seconds after the
compressor ON
4. Presumable cause
•
Broken sensor harness
•
Disconnection of sensor
harness connection
(connector)
•
Sensor (PSH, PSL) anomaly
•
Outdoor control PCB anomaly
•
Anomalous installation
conditions
•
Insufficient airflow volume
•
Excessive or insufficient
refrigerant amount
Note:
*1 E54-1: 1 time flash (PSL), E54-2 : 2 time flash (PSH)
[ ]
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...