Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
93
–
E60
E60-1
Rotor position detection failure
(CM1)
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Can
the compressor
startup?
Is
power supply voltage
OK?
Is the
sound and vibration of
the compressor
normal?
Is it
operated normally
without occurrence
of E60?
Does E42 occur?
Does E59 occur?
Reset the power supply and restart operation
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Save data for 30 minutes before stopping in Mente PC
( anomalous sound and vibration )
Check and save the data of
operating conditions
Correct it
Check it as much as
possible under the
operating conditions for
30 minutes before error
occurred
Correct it according to the
troubleshooting procedure
of E59
Correct it according to the
troubleshooting procedure
of E42
Replace compressor
Check the insulation
resistance and coil
resistance of compressor.
If necessary, replace
compressor
Replace compressor
Temporary malfunction by
noise.
2. Error detection method
Detection of the compressor
rotor position.
3.
Condition of error displayed
If it fails to detect the rotor
position of compressor, after
changinging over to the operation
of compressor rotor position
detection, the compressor stops.
When it is restart automatically
after 3 minutes delay, this
anomaly occurs 4 times within 15
minute after the initial detection
4. Presumable cause
• Compressor anomaly
• Inverter PCB anomaly
• Anomaly of power supply
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...