Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
94
–
E63
E63
Emergency stop
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Indoor unit
Diagnosis
Countermeasure
Is the
remote controller setting
of Emergency Stop
"Valid"?
Is ON
signal inputted to the
CnT terminal of indoor
control PCB?
Save data for 30 minutes before stopping in Mente PC
YES
NO
NO
YES
Check and save the data of
operating conditions
Check the conditions
whether it occurs
immediately after the power
on or during operation.
Replace remote control
PCB
Replace indoor control
PCB
Check the cause of
emergency stop.
(It is better to have the data
for 30 minutes before
stopping, when instructing
the installer)
2. Error detection method
When ON signal is inputted
to the CnT terminal of indoor
control PCB
3.
Condition of error displayed
Same as above
4. Presumable cause
Factors for emergency stop
Note:
Indoor unit detected emergency stop signal gives command "all stop"
Summary of Contents for 112KXE6
Page 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Page 134: ... 130 PJF012D003 ...
Page 135: ... 131 ...
Page 139: ... 135 PJA012D751 b ...
Page 140: ... 136 ...
Page 206: ... 202 2 model type DIS model type HEAD ...
Page 207: ... 203 2 2 ...
Page 208: ... 204 2 2 2 2 2 ...