107
–
E59
E59
Compressor startup failure
Keeps flashing
Stays Off
Keeps flashing 5 times flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is power
source voltage OK?
Is the
pressure balance at
starting OK?
Is the
insulation resistance
and coil resistance of
compressor
OK ?
Is power transistor
module OK?
NO (Inverter PCB is defective)
Is the
output of inverter
checker OK ?
Does it start?
Does
compressor startup?
Save data for 30 minutes before stoopping in Mente PC.
Try to restart several
times.
In case that the compressor
does not start at all and no
sound or vibration is heard
Start up by disconnecting
connector of outdoor
fan motor
Note : Several times restarting
may recover it, because liquid
refrigerant migrated in the
compresser is discharged from
the compressor.
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
After power OFF, turn JSW10-4 on the inverter PCB ON
and connect the inverter checker. And then power ON again.
(Regarding the checking method of inverter PCB with
inverter checker, refer to page 112 in detail)
Check and save the data of
operating conditions.
Replace outdoor fan motor.
Check power source
voltage.
Check refrigerant amount
and refrigerant circuit.
Repalce compressor.
Replace inverter PCB.
Replace inverter PCB.
Repalce compressor.
2. Error detection method
If it fails to change over to the
operation for rotor detection of
compressor motor
3. Condition of error displayed
If compressor fails to startup for
20 times (10 patterns x 2 times).
(It is availabel to reset by
remote control after 3 minutes
delay)
4. Presumable cause
•
Faulty fan motor
•
Faulty outdoor control PCB
•
Faulty inverter PCB
•
Anomalous power source
voltage
•
Nonconformity of refrigerant
amount and refrigerant circuit
•
Faulty compressor
Note:
Insulation resistance
• The unit is left for long period without power source or soon after installation, insulation resistance may decrease to
several MΩ or lower due to the liquid refrigerant migrated in the refrigerant oil in compressor. If the electric leakage
breaker is activated due to low insulation resistance, check followins.
➀
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated.)
➁
Check whether the electric leakage breake conforms to high-hermonic specifications
(As KXZE1 units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content