110
–
(b) Inverter PCB
1) FDC112, 140, 155KXZEN1 model
a) Exchange the PCB
after elapsing 3 minutes from power OFF
.
(
Be sure to measure voltage (DC)
on both capacitor terminals located in control back, and
check that the
voltage is discharged sufficiently
.(Refer to Fig.2))
b) Take off the connection of inverter PCB terminal block connector and remove the screw of power transistor then
remove the PCB. Wipe off the silicon grease neatly on the control’s radiation heat fins.
c) Refer to table1 for the setting of switch (JSW10,11) of new PCB.
d) Before installing the power transistor on the new PCB,apply uniformly a bundled of silicon grease first on the
surface of power transistor.Make sure it is applied to prevent damage on power transistor.
e) Tighten the screw of power transistor on inverter PCB and connect the terminal block.Confirm the connection
and don’t use soldering in the connection.Tighten properly the power transistor with a screw and make sure there
is no slack.Power transistor can be damage if not properly tighten.(Recommended power transistor tightening
torque:0.98-1.47N∙m)
TB1
TB11
Parts No.
Fig.1 Parts arrangement view
Fig.2 Position of capacitor
TB2
TB10
TB5
TB6
Connector
CNI2
CNI4
TB7
TB8
TB9
Voltage measurement parts
JSW10
Switch
JSW11
CNACT1
Terminal block
Terminal block
PCA565A151-1
-1
OFF
-1
ON
-2
OFF
-2
OFF
-3
OFF
-3
OFF
JSW10
-4
OFF
JSW11
-4
ON
Table. 1 Switch setting