112
–
■
Function of dip switch for contol (SW3, 4, 5)
• SW3 (Function setting)
Switch
Function
SW3-1
ON
Inspection LED reset
OFF
Normal
SW3-5
ON
Check operation start
OFF
Normal
SW3-7
ON
Forced cooling/heating
OFF
Normal
• SW4 (Change demand ratio)
Switch
Function
SW4-7
ON
SW4-8
OFF Compressor capacity
60
ON Compressor capacity
0
OFF
OFF Compressor capacity
80
ON Compressor capacity
40
■
Function of jumper wire (J13, 15)
(With: Shorted / None: Opened)
Jumper
Function
J13
With
External input Level input
None
External input Pulse input
J15
With
Defrost time Normal
None
Defrost time Cold weather region
■
Function of connector
• SW4 (Model selection)
Model
Switch
FDC112KXZE1 FDC140KXZE1 FDC155KXZE1
SW4-1
OFF
ON
OFF
SW4-2
OFF
OFF
ON
• SW4 (Overseas)
Model
Switch
All models
SW4-3
ON
• SW4 (Power source voltage)
Model
Switch
FDC112KXZEN1
FDC140KXZEN1
FDC155KXZEN1
FDC112KXZES1
FDC140KXZES1
FDC155KXZES1
SW4-4
ON
OFF
• SW5 (Function setting)
Switch
Function
SW5-1
ON
Test run switch
Test run
OFF Test run switch
Normal
SW5-2
ON
Test run operation mode
Cooling
OFF Test run operation mode
Heating
SW5-3
ON
Pump down switch
Pump down
OFF Pump down switch
Normal
• SW7, 8, 9 (Function setting)
Switch
Function
SW7
Data erase/data write
SW8
7-segment dispalay No. UP
order of 1
SW9
7-segment dispalay No. UP
order of 10
Connector
Function
Connector
Function
CNA1
Power source
CNL1
High pressure sensor
CNQ1
High pressure switch (CN1)
CNP1
Power transistor temperature thermistor
CNW
Open phase
CNEEV1
Heating EEV
CNN1
4-way valve
CNEEV2
Sub-cooling coil EEV
CNR1
Crankcase heater
CNX1
Superlink signal
CNA2
Power fan motor
CNF1
Sub-cooling coil temperature thermistor (liquid)
CNS1
External input
CNF2
Sub-cooling coil temperature thermistor (gas)
CNL2
Low pressure sensor
'17 • KX-SM-272
Summary of Contents for 140KXZEN1
Page 153: ... 17 KX SM 272 151 ...
Page 154: ... 17 KX SM 272 152 ...
Page 155: ... 17 KX SM 272 153 ...
Page 156: ... 17 KX SM 272 154 ...
Page 165: ... 163 MEMO 17 KX SM 272 ...