–
125
–
(1) When one outdoor unit is used.
(3) The signal lines can also be connected using the method shown below.
Indoor and outdoor signal wires
○
Indoor and outdoor signal lines do not have a polarity.
Any of the connections in the following illustration can be made.
(2) When plural outdoor units are used
Outdoor unit
Outdoor unit
Signal line
Refrigerant pipe
Network connector
Network connector
Earth wire is giving slack.
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor signal line
terminal block
Indoor signal line
terminal block
○
Loop wiring prohibited.
The signal lines cannot form a
loop, so the wirings shown as
....... in the diagram are
prohibited.
Power cable and signal line connection
Signal terminal block
Wiring label
●
The wiring label is attached on the back side of the service panel.
Outgoing cable direction
●
It holds cables in place and protect the terminal connection from external force.
●
As like the refrigerant pipe, it can be let out in any of the following directions:
side right, front, rear and downward.
●
Give adequate slack to cables in fastening them.
M4 screw
Important
●
Connect the signal line between indoor unit and outdoor unit to A1 and B1.
●
Connect the signal line between outdoor units to A2 and B2.
●
Please use a shielded cable for a signal line and connect a shielding earth at all the indoor units and outdoor units.
A
1 B1
A1・B1 A2・B2
A1
B1
A1
B1
A B
A B
A B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A1・B1 A2・B2
A1・B1 A2・B2
7-1. Unit address setting
Cable clamp
※
1 Signal line between the indoor unit and the outdoor unit.
※
2 Signal line between the outdoor units.
※
1
※
2
Attention
12 mm or less
FDC112
-
155KXZEN1 (Single-phase)
FDC112
-
155KXZES1 (Three-phase)
For M5
9.5 mm or less
For M4
For M3.5
6.6 mm or less
●
For cabling of the power source terminal block,
use crimp terminals of the figure shown below.
●
For cabling of the signal line terminal block,
use crimp terminals of the figure shown below.
Remote control wiring specifications
Length (m)
100 to 200
to 300
to 400
to 600
Wire size
0.5
mm
2
×
2 cores
0.75
mm
2
×
2 cores
1.25
mm
2
×
2 cores
2.0
mm
2
×
2 cores
Specification
250V 30A
Part No.
SSA564A161
(1) For the remote control the standard wire is 0.3mm
2
x 2 cores. The max. length is up
to 600m. When the wire is more than 100m long, use the wire shown in the table.
Main fuse specification
7. CONTROL SETTINGS
This control system controls the controls of more than one air-conditioner's outdoor unit, indoor unit and remote control unit through communication control, using the
microcomputers built in the respective controls. Address setting needs to be done for both outdoor and indoor units. Turn on power in the order of the outdoor units and
then the indoor units.
Use 1 minute as the rule of thumb for an interval between them.
The communication protocol can be choosen from following two types. One of them is the conventional Superlink (hereinafter previous SL) and the other is the new
Superlink
Ⅱ
(hereinafter new SL). These two communication protocols have their advantages and restrictions as summarized in a table in “6. ELECTRICAL WIRING
WORK” so please choose a desirable one meeting your installation conditions such as connected indoor units and central control.
When signal cables are connected into a network involving outdoor units, indoor units or central control equipment that do not support new SL, please select
communications in the previous SL mode, even if the refrigerant system is separated from theirs.
When communication is established after setting addresses, check the communication protocol with the 7-segment display panel of the outdoor unit.
'17 • KX-SM-272
Summary of Contents for 140KXZEN1
Page 153: ... 17 KX SM 272 151 ...
Page 154: ... 17 KX SM 272 152 ...
Page 155: ... 17 KX SM 272 153 ...
Page 156: ... 17 KX SM 272 154 ...
Page 165: ... 163 MEMO 17 KX SM 272 ...