6. To remove the drain pump(DM) and flot switch(FS)
(1) Remove the drain pan.(See No.5)
(2) Pull a hose to the arrow direction and remove it.
(3) Remove 3 drain pump fixing screws and remove it.(
mark)
(4) Remove the flot switch fixing screw and remove it.(
mark)
7. To remove the thermistors (example"Thi-R1")
(1) Remove the drain pan.(See No.5)
(2) Pull out the thermistor"Thi-R1" from
the sensor holder.
8. To remove the heat exchanger assembly
(1) Remove the drain pan.(See No.5)
(2) Remove 2 pipe lid fixing screws and remove it.(
mark)
(3) Remove 3 heat exchanger assembly fixing screws and remove it.(
mark)
9. To remove the Electronic Expansion Valve (EEV)
(1) Remove the heat exchanger assembly.(See No.8)
(2) Remove the coil of EEV by pull out on the top.
(3) Remove welded part of EEV by welding.(
mark)
PROCEDURE & PICTURES
General view
Pipe lid
EEV
Coil of EEV
'17 • KX-SM-272
–
1
40
–
#
Summary of Contents for 140KXZEN1