7. To remove drain pump (DM)
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the drain pump connector(CNR)
on PCB in control box.
(3) Remove 4 drain pump assembly fixing
screws and remove it.(
mark)
(4) Pull a hose to the arrow direction and
remove it.
(5) Remove 3 drain pump fixing screws and
remove it.(
mark)
8. To remove the thermistors (example"Thi-R1")
(1) Remove the lid of control box.(See No.1)
(2) Disconnect the Tho-R1 connector(CNNx) on PCB in control box.
(3) Remove the drain pan.(See No.3)
(4) Pull out the thermistor"Thi-R1" from the sensor holder.
9. To remove the heat exchanger assembly
(1) Remove the drain pan.(See No.3)
(2) Remove 4 pipe lid fixing screws
and remove it.(
mark)
(3) Remove 4 heat exchanger assy fixing
screws and remove it.(
mark)
10. To remove the electronic expansion Valve (EEV)
(1) Remove the heat exchanger assembly.
(See No.7)
(2) Remove the coil of EEV by pull out
on the top.
(3) Remove welded part of EEV by welding.
(
mark)
PROCEDURE & PICTURES
Pipe lid
c
EEV
Coil of EEV
General view
'17 • KX-SM-272
–
1
4
4
–
#
Summary of Contents for 140KXZEN1