–
20
–
'17 • KX-SM-272
(20) Selection of cooling/heating external input function
(a) When “External input 1 setting: Cooling/heating” is set for the indoor unit function from remote control, the cooling or
heating is selected with CnT-6 or CnTA.
(b) When the External input 1 method selection: Level input is set for the indoor unit function:
・
CnT-6 or CnTA: OPEN → Cooling operation mode
・
CnT-6 or CnTA: CLOSE → Heating operation mode
(c) When the External input 1 method selection: Pulse input is set for the indoor unit function:
If the external input is changed OPEN → CLOSE, operation modes are inverted (Cooling → Heating or Heating →
Cooling).
(d) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
External input selection
External input selection
Cooling/heating selection
External input method
⑤
Level
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
⑥
Pulse
Operation
OFF
Cooling zone
Heating zone
Cooling zone
Cooling zone
Heating zone
Heating zone
OFF
ON
OFF
OFF
ON
ON
ON
Cooling
Heating
Heating
Cooling
Cooling
Cooling
Auto
Auto
Cooling
Auto, cooling, dry mode
↑
command from remote control
↑
Heating, auto, heating mode
command from remote control
↑
Set “Cooling/
Heating” “Pulse”
↑
Auto, cooling, dry mode
command by remote control
↑
Auto, heating mode
command by remote control
↑
After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode.
During heating:: Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Heating
Cooling
Heating
Cooling
Cooling
Note (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 16.
(21) Room temperature detection temperature compensation during heating
With the standard specification, the compressor is turned ON/OFF with the thermostat setting temperature. When the thermostat
is likely to turn OFF earlier because the unit is installed at the ceiling where warm air tends to accumulate, the setting can be
changed with the wired remote control indoor unit function “
”. The compressor and the heater are turned ON/OFF at
one of the setting tempe3, +2 or +1°C in order to improve the feeling of heating. The setting temperature, however, has
the upper limit of 30°C.
Compressor
Compressor
Standard
Operation
Stop
Setting temperature
-1
+1
Room temperature (deg)
Operation
Stop
Setting temperature
+2
+4
Room temperature (deg)
When it is set at +3°C
(22) Return air temperature compensation
This is the function to compensate the deviation between the detection temperature by the return air temperature thermistor and
the measured temperature after installing the unit.
(a) It is adjustable in the unit of 0.5°C with the wired remote control indoor unit function “RETURN AIR TEMP”.
• +1.0°C, +1.5°C, +2.0°C
• -1.0°C, -1.5°C, -2.0°C
(b) Compensated temperature is transmitted to the remote control and the compressor to control them.
Note (1) The detection temperature compensation is effective on the indoor unit thermistor only.
Summary of Contents for 140KXZEN1
Page 153: ... 17 KX SM 272 151 ...
Page 154: ... 17 KX SM 272 152 ...
Page 155: ... 17 KX SM 272 153 ...
Page 156: ... 17 KX SM 272 154 ...
Page 165: ... 163 MEMO 17 KX SM 272 ...