22
–
'17 • KX-SM-272
(31) Indoor unit overload alarm (RC-EX3 only)
If the following condition is satisfied at 30 minutes after starting operation, RC-EX3 shows maintenance code "M07" and the
signal is transmitted to the external output (CnT-5).
(a) Receipt of the signal by the external output is indicated by lighting an LED or other prepared on site.
・
Cooling, Dry, Auto(Cooling) : Indoor air temperature = Set room temperature by remote c Alarm temperature difference
・
Heating, Auto(Heating) : Indoor air temperature = Set room temperature by remote control - Alarm temperature difference
Alarm temperature difference is selectable between 5 to 10°C.
(b) If the following condition is satisfied or unit is stopped, the signal is disappeared.
・
Cooling, Dry, Auto(Cooling) : Indoor air temperature = Set room tempe Alarm temperature difference -2°C
・
Heating, Auto(Heating) : Indoor air temperature = Set room temperature - Alarm temperature diff2°C
(32) Peak-cut timer (RC-EX3 only)
Power consumption can be reduced by restricting the maximum capacity.
Set the [Start time], the [End time] and the capacity limit % (Peak-cut %).
・
4-operation patterns per day can be set at maximum.
・
The setting time can be changed by 5-minutes interval.
・
The selectable range of capacity limit % (Peak-cut %) is from 0% to 40-80% (20% interval).
・
Holiday setting is available.