41
–
Code
No.
Contents of data display
Data display range
Minimum
unit
Remarks
<User setting>
P00 (Spare)
– – – –
–
P01 Operation preference switching
0 : (Factory default)
0,1
–
0: First push preference (Factory default)
1: Last push preference
P02 Outdoor fan snow protection control
0 : (Factory default)
0,1
–
0: Outdoor fan snow protection control invalid
(Factory default)
1: Outdoor fan snow protection control valid
P03
Outdoor fan snow protection control
ON time setting
30 : (Factory default)
10, 30 - 600 [Sec]
30
Changes like 10, 30, 60 90 … 600
P04 Demand ratio change value
OFF : (Factory default)
OFF,000,040,
060,080
0: OFF, 1: 0%, 2: 40%. 3: 60%, 4: 80%
Factory default is 0: OFF.
P05 Silent setting
0 : (Factory default)
0 - 9
1
P06 External output function quota
0 : (Factory default)
0 - 9
1
P07
External input (CnS1) function
quota
0 : (Factory default)
0 - 9
1
P08
(Spare)
External input (CnS2) function
quota
1 : (Factory default)
0 - 9
1
P09
(Spare)
External input (CnG1) function
quota
2 : (Factory default)
0 - 9
1
P10
(Spare)
External input (CnG2) function
quota
3 : (Factory default)
0 - 9
1
'17 • KX-SM-272