82
–
E12
Address setting error
by mixed setting method
Keeps flashing 1 time flash
Keeps flashing
Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't the
auto setting and the
manual setting mixed in the address
setting method for indoor
units?
YES
NO
Review address setting.
Replace indoor control
PCB.
2. Error detection method
Auto (remote control) setting
and manual setting are mixed in
the address setting method for
indoor units
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake in address setting for
indoor unit
Note:
Address setting method list (Figures in [ ] are for old Superlink models)
Models for new Superlink protocol
Models for old Superlink protocol
Indoor unit address setting Outdoor unit
address setting Indoor unit address setting
Outdoor unit
address setting
Indoor unit
No. switch
Outdoor unit
No. switch
Outdoor unit
No. switch
Indoor unit
No. switch
Outdoor unit
No. switch
Outdoor unit
No. switch
Manual address setting
(New SL)
000-127
00-31
00-31
00-47
00-47
00-47
(Old SL)
[00-47]
[00-47]
[00-47]
Auto address setting for
single refrigerant system
(New SL)
000
49
49
49
49
49
(Old SL)
Auto address setting for
multiple refrigerant systems
(New SL)
000
49
00-31
Not available
(Old SL)
Not available
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content