IU Back-up function
In case of 2 sets of indoor units connected to one R/C, it is available to
perform back-up operation with them.
IU rotation: Operate 2 sets of indoor units alternately at every set time
of operation interval.
Set the timer for changeover
➝
⑳
IU capacity back-up: When the temp difference between the set temp
and the actual room temp is higher than the set temp
diff., 2 sets of indoor units operate. When the temp
difference reaches to the set temp diff. it is switched to
one unit operation.
Set the temp diff. for back-up
➝
IU fault back-up: If one of the IU has a fault and stops, the other one
starts operation.
[Enable/Disable] setting of each function can be done.
When [IU rotation] or [IU capacity beck-up] is set [Enable], [IU fault
back-up] is set [Enable] automatically.
⑳
Set the timer for changeover
In IU rotation function, the timer to changeover the operation of 2
indoor units is set.
Set the temp diff. for back-up
In IU capacity back-up function, the temperature difference between
the temp to start operation of 2 indoor units and the set temp is set.
(Setting range 2-5°C)
⑲
IU Back-up function
⑳
Set the timer for changeover
Set the temp diff. for back-up
Summary of Contents for eco touch RC-EX1A
Page 1: ...eco touch REMOTE CONTROL RC EX1A RC EX1N INSTALLATION MANUAL PJZ012D077 B ...
Page 48: ...eco touch FERNBEDIENUNG RC EX1A RC EX1N INSTALLATIONSANLEITUNG PJZ012D077A B ...
Page 95: ...Télécommande à distance TD eco touch RC EX1A RC EX1N Notice d installation PJZ012D077B B ...
Page 142: ...MANDO A DISTANCIA eco touch RC EX1A RC EX1N MANUAL DE INSTALACIÓN PJZ012D077C B ...
Page 189: ...FILOCOMANDO eco touchRC EX1A RC EX1N MANUALE DI INSTALLAZIONE PJZ012D077D B ...
Page 236: ...eco touch AFSTANDSBEDIENINGRC EX1A RC EX1N INSTALLATIEHANDLEIDING PJZ012D077F B ...
Page 283: ...eco touch UZAKTAN KUMANDA RC EX1A RC EX1N KURULUM KILAVUZU PJZ012D077G B ...
Page 330: ...CONTROLO REMOTO eco touch RC EX1A RC EX1N MANUAL DE INSTALAÇÃO PJZ012D077H B ...