−54−
■
When error happens
A list of error code
Remote
controller
Error code
LED on heat pump unit
7-segment
display
Contents of inspection
Green
Red
No display
Keep flashing
Stay off
Normal
Power line anomaly
No display
E1
Keep flashing
Stay off
Normal
Communication error between remote controller and heat pump unit
E10
Keep flashing
Stay off
Normal
Excessive connected number of heat pump units to the remote controller
E31
Keep flashing
1-time flash
E31
Duplicated address No. of heat pump unit
Address setting error of heat pump unit
E32
Keep flashing
1-time flash
E32
Open phase on power source
Reverse phase on power source
E36
Keep flashing
1-time flash
E36-1
Discharge pipe temperature anomaly (Tho-D1)
E37
Keep flashing
1-time flash
E37-1
Heat exchanger temp. sensor 1 fault (Tho-R1)
2-time flash
E37-2
Heat exchanger temp. sensor 2 fault (Tho-R2)
3-time flash
E37-3
Heat exchanger temp. sensor 3 fault (Tho-R3)
4-time flash
E37-4
Heat exchanger temp. sensor 4 fault (Tho-R4)
5-time flash
E37-5
Fault of inlet water temp. sensor 1 on gas cooler (Tho-W1)
6-time flash
E37-6
Fault of outlet water temp. sensor 2 on gas cooler (Tho-W2)
Keep flashing
E37-7
Fault of inlet gas temp. sensor 1 on gas cooler (Tho-G1)
E37-9
Fault of outlet gas temp. sensor 3 on gas cooler (Tho-G3)
E38
Keep flashing
1-time flash
E38
Outdoor air temp. sensor fault (Tho-A)
E39
Keep flashing
1-time flash
E39-1
Discharge pipe temp. sensor fault (Tho-D1)
3-time flash
E39-3
Fault of inlet temp. sensor 1 on intermediate receiver (Tho-M1)
E40
Keep flashing
1-time flash
E40
High pressure anomaly (HP switch 63H1-1 activated)
E41
Keep flashing
1-time flash
E41-1
Power transistor overheat (for CM1) (5 times within 60 minutes)
E42
Keep flashing
1-time flash
E42-1
Current cut (for CM1)
E45
Keep flashing
1-time flash
E45-1
Communication error between inverter PCB and control PCB (CM1)
High pressure anomaly (HP switch 63H-1 activated)
E48
Keep flashing
1-time flash
E48-1
Outdoor fan motor 1 anomaly (FMo1)
2-time flash
E48-2
Outdoor fan motor 2 anomaly (FMo2)
E49
Keep flashing
1-time flash
E49-1
Low pressure anomaly (LP sensor PSL1 activated)
E51
Keep flashing
1-time flash
E51-1
Power transistor 1 overheat (for CM1) (15 minutes continuously)
E52
Keep flashing
1-time flash
E52-1
Fault of hot water temp. sensor 1 on unvented cylinder (Tht-1)
2-time flash
E52-2
Fault of hot water temp. sensor 2 on unvented cylinder (Tht-2)
3-time flash
E52-3
Fault of hot water temp. sensor 3 on unvented cylinder (Tht-3)
4-time flash
E52-4
Fault of hot water temp. sensor 4 on unvented cylinder (Tht-4)
5-time flash
E52-5
Fault of hot water temp. sensor 5 on unvented cylinder (Tht-5)
6-time flash
E52-6
Fault of hot water temp. sensor 6 on unvented cylinder (Tht-6)
Keep flashing
E52-7
Fault of hot water temp. sensor 7 on unvented cylinder (Tht-7)
E52-8
Fault of hot water temp. sensor 8 on unvented cylinder (Tht-8)
E52-9
Fault of hot water temp. sensor 9 on unvented cylinder (Tht-9)
E53
Keep flashing
1-time flash
E53-1
Suction pipe temp. sensor 1 fault (Tho-S1)
3-time flash
E53-3
Injection inlet temp sensor 1 fault (Tho-inj1)
E54
Keep flashing
1-time flash
E54-1
Disconnection of low pressure sensor 1(PSL)
Anomalous output of low pressure sensor 1
2-time flash
E54-2
Disconnection of high pressure sensor 1(PSH)
Anomalous output of high pressure sensor 1
3-time flash
E54-3
Disconnection of intermediate pressure sensor 1(PSM)
Anomalous output of intermediate pressure sensor 1
E55
Keep flashing
1-time flash
E55-1
Under-dome temp. sensor 1 fault (Tho-C1)
E56
Keep flashing
1-time flash
E56-1
Power transistor temp. sensor 1 fault (Tho-P1)
E58
Keep flashing
1-time flash
E58-1
Compressor anomaly by loss of synchronism (CM1)
E59
Keep flashing
1-time flash
E59-1
Compressor start-up failure (CM1)