2. Technical specifications
Model FD-PAC / FDC71VN
Model
Technical specifications
Control kit
Outdoor unit
FD-PAC FDC71VN
Nominal coolingcapacity
(1)
W
7100 (3200 ~ 8000)
Nominal heating capacity
(1)
W
8000 (3600 ~ 9000)
Power source
1 fase, 220/230/240V, 50Hz, N, PE
Opera
tio
n da
ta (
3
)
Cooling power consumption
kW
2,01/2,01
Running current (cooling)
A
8,9/9,2
Power factor (cooling)
%
98/99
Heating power consumption
kW
2,21/2,21
Running current (heating)
A
9,8/10,2
Power factor (heating)
%
99
Inrush current
A
5,0
Moise level
dB(A)
-
48
Exterior dimensions (height x width x depth)
mm
400 x 300 x 120
750 x 968 x 340
Nett weight
Kg 8
60
Compressor type
-
-
Compressor motor
kW
-
-
Refrigerant oil
L -
(M-MA32R)
Carterheating
W
-
33 (carterheating)
Starting method
-
Direct
Heat exchanger
-
Air (straight fin)
Defrost control
Microprocessor controller de-icer
Refrigerant
R410A
Refrigerant amount
kg
-
2,95 (pre-charged to 30 mtr)
Refrigerant expansion
Elektronic expansion valve
Air handling equipment, fan type
-
Axial fan x 1
Motor
-
55 x 1
Air flow
m³/h Min.1200
3600
Air entrance temperature cooling min./ max.
°C
16 / 32
-
Air entrance temperature heating min./ max.
°C
10 / 32
-
Water entrance temperature cooling min./
max.
°C
16 / 32
-
Water entrance temperature heating min./
max.
°C
10 / 32
-
Safety equipment
-
Internal thermostat for fanmotor,
anomalous discharge temperature
protection
Refrigerant piping
mm
Liquid line 10mm, Gas line 16mm
Piping size
mm
Liquid line 9,52 mm (3/8”), Gas line 15,88mm (5/8”)
Connecting method
Flare piping
Isolation
Necessary (liquid and gasline)
Drain hose
mm
-
Drain pan3x Ø20 mm
Accessoires
-
Paneel (separate packing)
-
Optional accessoires
-
-
Remote controller
RC-E3
-
Notes
(1) The data are measured at the following conditions.
Item
Mode
Indoor temperature
Outdoor temperature
standard
d.b. temp.
w.b. temp.
d.b. temp.
w.b. temp.
Cooling 27°C
19°C
35°C
24°C
ISO-T1, JIS
B8616
Heating 20°C - 7°C 6°C
(2) This airconditioner is manufactured and tested in conformity with the following standards: ISO-T1”unitary
airconditioner”.
(3) The operation data indicate when the airconditioner is operated at 230V, 50hz.
(4) Values in ( ~ ) show the minimum to maximum range.
(5) Adjustment of the estimated output via DIP switch (see page 16).
-
6
-
Summary of Contents for FD-PAC
Page 1: ...Technical manual Version 01 10 FD PAC Controlkit R410A FDC71 250V FD PAC ...
Page 15: ...3 3 Lay out plate heat exchanger ...
Page 16: ...3 4 Lay out heat exchanger ...
Page 17: ...3 4 Lay out wiring diagram ...
Page 18: ...4 Troubleshooting ...
Page 19: ... 19 ...
Page 20: ... 20 ...
Page 21: ... 21 ...
Page 22: ... 22 ...