20
-
10
Error display :
e28
[Directive remote controller thermistor.]
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
Green LED
Stays OFF
Keeps flashing
Outdoor unit
Detectivie remote controller PCB
Replacement (Detective re-
mote thermistor input circuit)
YES
NO
NO
YES
Detective remote controller
thermistor Replacement
Are characteristics of
remote controller therm-
istor OK or is there any
broken wire?
Is the remote controller
thermistor connector co-
nnection OK?
Correction
Temperrature(
°
C)
0
1
2
4
6
8
10
12
Resistance value (k
Ω
)
65
62
59
53
48
44
40
36
Temperrature(
°
C)
14
16
18
20
22
24
26
28
Temperrature(
°
C)
30
32
34
36
38
40
42
44
Temperrature(
°
C)
46
48
50
52
54
56
58
60
Resistance value (k
Ω
)
33
30
27
25
23
21
19
18
Resistance value (k
Ω
)
16
15
14
13
12
11
9.9
9.2
Resistance value (k
Ω
)
8.5
7.8
7.3
6.7
6.3
5.8
5.4
5.0
Resistance-temperature characteristic of remote controller thermister
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.