Preset point of the protective devices
Parts name
Mark
Equipped
unit
40, 50, 60 model
71, 100, 125, 140 model
Thermistor
(for protection
overloading in heating)
ThI-R
ާ
TH1
ި
ThI-R
ާ
TH2
1
ި
Indoor unit
ON 63
㷄
OFF 56
㷄
ON 17
㷄
OFF 16
㷄
Thermistor
(for frost prevention)
ON 1.0
㷄
OFF 10
㷄
Thermistor
(for protection high
pressure in cooling.)
Tho-R
(TH1)
Outdoor unit
ON 65
㷄
OFF 51
㷄
ON 63
㷄
OFF 53
㷄
Thermistor
(for detecting discharge
pipe temp.)
Tho-D
(TH3)
Outdoor unit
ON 115
㷄
OFF 85
㷄
ON 115
㷄
OFF 95
㷄
㵪
㵪
High pressure switch
(for protection)
63H1
Outdoor unit
ON 4.15MPa
OFF 3.15MPa
Low pressure sensor
(for protection)
LPT
Outdoor unit
ON 0.079MPa
OFF 0.227MPa
Notes(1) Values in ( ) shown in the case of 40, 50, 60 models.
(2) Values in
〔 〕
shown in the case of SRK.
ON 2.5
㷄
OFF 8
㷄